Overview
The Foundry Relay Controller offers DMX controlled fully-rated 20 A relays to switch lighting loads on and off. The Relay Controller mounts to an electrical junction box.
APPLICATIONS
- Arena and stadium suites
- Office buildings
- Conference and meeting rooms
- Healthcare facilities
- Houses of worship
- Classrooms
- Hospitality and restaurants
- Retail
FEATURES
- Switched power control of two circuits
- 20 A fully-rated relays for use with general purpose, tungsten, fluorescent, and LED loads
- Supports plug loads
- 120–277 VAC power input
- DMX controlled and RDM configurable
COMPLIANCE
- ULus Listed
- Rated for plenum use
Specifications
FUNCTIONAL
- Control for individual fixtures, zone power
- Supports USITT DMX512-A (ANSI E1.11)
- Supports RDM (ANSI E1.20)
MECHANICAL
- Constructed of injection-molded ABS plastic
- Button interface and LED indicators for configuration
- Half-inch conduit knockout mounted
- Mains-voltage wiring exits through knockout mount
- 0–10 V dimming control wiring exits through knockout mount
- DMX wiring connects to side of controller
- Mains power input connections:
- Hot (black wire) - 4 mm2 (12 AWG)
- Neutral (white wire) - 2.5 mm2 (14 AWG)
- Relay output connections:
- Zone 1 (red wire) - 4 mm2 (12 AWG)
- Zone 2 (red/white wire) - 4 mm2 (12 AWG)
- Optional mounting plate available for applications that require low-voltage wiring to be installed in conduit
ELECTRICAL
- 120–277 VAC, 50/60 Hz, 1 pole power input
- Normally Open (NO) 20 A, fully-rated relay
- Supports lighting and plug loads
DMX INPUT PORT
- Optically-isolated from controller electronics
- Withstands fault voltages of up to 250 VAC
- Integrated DMX/RDM termination
CONFIGURATION
- Remote configuration available via RDM controllers including:
- ETC DMX/RDM gateway networked to a device running ETC Concert software
- ETC control console with RDM functionality
- -Third-party configuration and control products
- Manual configuration of the starting DMX address on the controller
THERMAL
- Ambient room temperature: 0°C to 50°C (32°F to 122°F)
- Ambient humidity: 5%–95%, non-condensing