Overview
The Foundry Mini Panels offer up to eight zones of DMX controlled lighting with fully rated 20 A relays and optional 0–10 V control per zone. The Mini Panel features a Demand Response input for energy saving integration and a UL 924 emergency lighting control bypass with power loss sense. The Mini Panel is available in flush-mount or surface-mount options and can be located in an air plenum to be easily tucked out of sight.
APPLICATIONS
- Arena and stadium suites
- Office buildings
- Conference and meeting rooms
- Healthcare facilities
- Houses of worship
- Classrooms
- Hospitality and restaurants
- Retail
FEATURES
- Switched power control of four or eight circuits with 0–10 V dimming
- 120 or 277 VAC power input per zone
- 20 A fully rated relays for use with general purpose, tungsten, fluorescent, LED and plug loads
- 0–10 V dimming output per zone for direct connection to dimming ballasts and LED drivers
- Demand Response load shedding contact input
- Flush-mount and surface-mount options
- UL924 control bypass via
- Contact closure input
- Normal power loss sense feed terminals
- DMX controlled and RDM configurable
REGULATORY AND COMPLIANCE
- cULus and UL 924 LISTED
- Rated for plenum installation
- Suitable for plug load control
Specifications
FUNCTIONAL
- Control for up to eight zones of switching for lighting and plug loads
- Control for up to eight zones of 0–10 V dimming for LED drivers and fluorescent ballasts
- UL 924 emergency-lighting control via contact closure and power loss sense feed terminal
- Demand Response input provided by a power company can enforce a maximum level per circuit while active
- Supports USITT DMX512-A (ANSI E1.11)
- Supports RDM (ANSI E1.20)
MECHANICAL
- Constructed of 16-gauge cold-rolled steel, finished in fine-textured, black powder coat
- Wall-mount installation; rated for installation in plenum air space
- Class 1 voltage barrier prevents access to line-voltage wiring with front panel removed
- Available in flush-mount and surface-mount options
- Optional voltage divider allows for separation of normal and emergency circuits in a single controller where allowed by local codes
ELECTRICAL
- 100–277 VAC, 50/60 Hz power input per circuit with support for pass thru to multiple circuits
- 100–277 VAC single phase sense feed input
- Supports 120 VAC and 277 VAC circuits within the same panel
- 20 A, fully-rated bi-state latching relay per output
- 0–10 VDC control rated for up to 100 mA sink per output
- 0–10 V outputs are fully isolated from ground to 2500 V RMS
- Control circuit power draw: 0.5A
- Rising clamp screw terminal wiring connections for:
- Line-voltage relay power input, output and pass-through with support for 2.5-10 mm2 (14-8 AWG) wire
- Controller power input and UL 924 Sense circuit with support for 0.5-4 mm2 (20-12 AWG) wire
- Low-voltage 0–10 V dimming output per zone with support for 0.5-1.5 mm2 (22-16 AWG) wire
- Separate normal power sense feed input for UL 924 emergency lighting bypass
- UL 924 emergency lighting control contact closure input with support for 0.5-1.5 mm2 (22-16 AWG) wire
- Demand Response contact input with support for 0.5-1.5 mm 2 (22-16 AWG) wire
- Demand Response input supports Normally Open (NO) operation
- UL 924 contact closure input supports normally open (NO) or normally closed (NC) operation
- Onboard status indicators for controller power, DMX signal, Demand Response input, and UL 924 emergency lighting control
- Slide switch configuration for:
- UL 924 operation (NO/NC)
- UL 924 inclusion per circuit (on/off)
RELAY RATINGS
- 20 A Magnetic Ballast (HID)
- 16 A Electronic Ballast
- 20 A Tungsten
- 20 A (120 A Locked-rotor) Motor @ 120 VAC
- 14 A (84 A Locked-rotor) Motor @ 277 VAC
- Relays are mechanically held
- Lifespan:
- 100,000 cycles at full resistive load
- 30,000 cycles motor, inductive or tungsten
DMX INPUT PORT
- Optically-isolated input from the Mini Panel electronics
- Withstands fault voltages of up to 250VAC
- Integrated DMX/RDM termination
CONFIGURATION
- Remote configuration available via RDM devices such as:
- ETC control console with RDM functionality
- ETC DMX/RDM gateway networked to a device running ETC Net3 Concert software
- Manual configuration of the starting DMX address, UL 924 bypass, and Demand Response on the controller
THERMAL
- Ambient room temperature: 0°–50° C (32°–122° F)
- Ambient humidity: 5–95% (non-condensing)