Overview
Buildings waste electricity as a result of lights being left on in an unoccupied room. Occupancy and Vacancy Sensors are a convenient and simple solution for any facility to eliminate wasted energy by automatically turning off lighting loads when a room is empty. The low-profile, sleek sensors can be installed anywhere to provide uninterrupted, 24/7/365 operation, without affecting the look and beauty of their surroundings.
APPLICATIONS
- Houses of worship
- Education
- Hospitality
- Healthcare facilities
- Office buildings
- Conference rooms
- Meeting rooms
- Retail
Features
- Supports for occupancy or vacancy detection as required
- Mode programmed via commissioning software
- Passive infrared (PIR) and Acoustic sensing technology
- Two mounting options available:
- Ceiling-Mount
- Wall-Mount
- Multiple Lensing options available
- Walk-thru mode for coverage verification
- Field-installed coverage masks (Ceiling only)
- LinkConnect: two-wire, topology-free bus for power and communication
- Ceiling Sensor available in black and white
- Wall Sensor available in cream, black and white
REGULATORY AND COMPLIANCE
- UL and cUL LISTED
- CE marked
Specifications
FUNCTIONAL
- Supports software-configured Auto-On/Auto-Off functionality (occupancy sensing) or Manual-On/Auto-Off (vacancy sensing) functions
- Ceiling Sensor:
- 360-degree coverage pattern
- Includes configurable coverage masks
- Small room: 450 sq. ft. at 8’ ceiling, 800 sq. ft. at 12’ ceiling
- Large room: 1800 sq. ft. at 8’ ceiling, 3000 sq. ft. at 12’ ceiling
- High ceiling: 300 sq. ft. at 10’ ceiling, 7000 sq. ft. at 40’ ceiling
- Wall Sensors
- Wide: 60’ coverage at 7-10’ mounting height. 140 degree field of detection
- Narrow: 16’ by 75’ coverage pattern at mounting height of 7-10’. 40 degree field of detection
- Supports walk-thru mode for verifying coverage area
- Sensor lens illuminates for walk-thru and test mode operation
- Red illumination for PIR detection
- Green illumination for Acoustic Detection
- Sensor coverage tested to NEMA WD 7-2000
MECHANICAL
- Constructed of injection-molded, ABS plastic in Pure White (RAL9010), Black (RAL 9004) or Cream (RAL 9003 - Wall only)
- Electronics assembly and mounting accessories included
- Accessible configuration buttons
- No visible means of attachment
- Ceiling Mount:
- Surface- or box-mountable
- Supports drywall, plaster, wood and concrete mounting
- Mounts to standard electrical box (supplied by others)
- Mounts to compressed fiber ceilings with included wire mounting option
- Wall Mount:
- Flush-mount to industry standard backbox, RACO 690 or equivalent
ELECTRICAL
- Connect via LinkConnect two-wire control network utilizing low-voltage Class 2 wiring
- Topology-free and polarity-independent wiring over Belden 8471 or equivalent and one #14 ESD drain wire
- Wiring may be bus, loop, homerun or any combination of these
- All station terminations utilize removable connectors
ENVIRONMENTAL
- Ambient room temperature: 0–40° C (32–104° F)
- Ambient humidity: Maximum 90% non-condensing