Overview
ETC’s Sensor IQ Intelligent Breaker System provides mains-fed power distribution for up to 48 branch circuits in the industry’s most compact footprint. Sensor IQ breakers combine high-inrush rated overcurrent protection, switched power control, and power usage/breaker status reporting in a single device. With built-in station and sensor support via contact input, DMX and Ethernet connectivity, and optional 0–10 V dimming or DALI output, Sensor IQ panels easily integrate into a broad range of systems and applications.
APPLICATIONS
- Theaters
- Schools
- Houses of worship
- Conference centers
- Studios
- Arenas and stadiums
FEATURES
- Mains Feed: Three-phase 120/208 V four-wire plus ground or single (bi) phase 120/240 V three-wire plus ground
- 12-, 24- or 48-position breaker subpanel
- Breakers
- Hydraulic magnetic breaker with high inrush trip curve
- 22 kA SCCR (up to 65 kA series rated with main breaker)
- Freely mix one-, two- and three-pole breakers up to 30 A
- Integrated air-gap relay switching
- Integrated on/off/tripped and connected load feedback
- No power required for handle operation at the breaker
- 20 A single-pole intellingent breakers are suitable for plug load control
- DMX and Ethernet (sACN) control of preset and sequence playback
- Local user interface provides:
- Panel configuration
- Preset and sequence programming and playback
- Individual channel control
- Built-in Ethernet port
- Available 0–10 V, contact input, and DALI control cards
- UL924 Listed emergency control bypass with load shedding
Specifications
REGULATORY AND COMPLIANCE
- Breakers Listed to UL 489
- Enclosures listed to UL 67, UL 508, UL 924
- Complies with ANSI DMX512-A standard
- Complies with ANSI E1.31 streaming ACN standard
USER INTERFACE
- Graphical display
- Button interface
- 0–9 number entry
- Up, down and back-arrow navigation with enter
- Test shortcut for local activation of preset, sequence and
- set level overrides
- USB interface for uploads of setup and software updates
BREAKER
- Hydraulic magnetic breaker maintains trip curve through entire thermal range, reducing nuisance tripping Bus connection type: Stab on
- One, two or three poles
- UL 489 Listed
- 15, 20 or 30 A
- 50/60 Hz frequency
- Inrush-pulse tolerance: 25 times rated current for half-cycle
- Integrated hall-effect sensors detect contact positions
- Integrated solenoid for remote operation
- Trips on overload even if handle is forcibly held in the “on” position
- Load lugs accept 14-6 AWG load wiring
- Multi-conductor rated output terminal
- Integral mechanically held air gap relay
- Integral current sensing
- Integral position and trip sensing
- Supports manual control of relay state using breaker handle without power
- Control and status provided by contact pads directly at bottom of the breaker case. No external wires or connections required for control or feedback
- Remote Feedback for breaker state, breaker type, current draw and phase voltage
- Visible state indication:
MECHANICAL
- Enclosure constructed of 16-gauge steel finished in black, fine-textured, scratch-resistant powder coat paint
- Removable outer panel includes integral locking door to limit access to electronics, breakers and local relay overrides
- Full front access with no side clearance required
- Removable covers for access to Class 1 and Class 2 wiring
- Complies with California building code - seismic zone four
ELECTRICAL
- Mains feed power input to support 120/208 V three-phase four-wire or 120/240 V bi-phase three-wire plus ground•
- Max current input: 100 A at 12 circuits, 200 A at 24 circuits, and 400 A at 48 circuits
- Quiescent draw: <10 W with relays at steady state
- Optional isolation between chassis and equipment grounding
- Short-circuit current rating: 22,000 A or 65,000 A symmetrical (see chart a right)
- Overloads occurs at 50 operations of 600% of rated current
- Integrated current transformer
- Current measurement range of 1–30 A. The maximum crest factor of primary current is 2.5
- Feeder entry supported at top or top side
- Bottom or bottom side entry supported by rotating enclosure during installation
- Load wire entry supported on top, sides or bottom
ENVIRONMENTAL
- Thermal: 0°C to 40° C (32°F to 104° F) operating temperature
- 24 A circuit (30 A breaker) - 1.4 W, 4.8 BTU/hr
- 16 A circuit (20 A breaker) - 1 W, 3.4 BTU/hr
- Humidity; 5%–95%, non-condensing
- Complies with ESD immunity to IEC standard 1000-4-2
CONTROL ELECTRONICS
- Input: 120–277 V (+/-15%), 50/60 Hz, <16 A
- Multi-tap transformer terminals accept up to 12 AWG wire
- Control wiring terminations:
- Control terminals accept maximum of 12 AWG wire
- Control wiring exiting the panel are Class 2
- All control terminations utilize removable connectors
FUNCTIONAL
- System-Wide control
- DMX or sACN input
- Per-circuit patching
- Per-circuit threshold
- 0–200 prioritization
- Configurable data loss behavior:
- Play preset; Hold last look; Wait and fade
- UL 924 emergency lighting with load shedding
- Load shedding requires a UPS Control Backup Wiring Kit (7131K1817) and Uninterruptable Power Supply (UPS) by others
- UPS to supply 800 W–2400 W AC power to control processor
- Application/Space segmented Control
- Space segmenting: up to 16 spaces per panel
- Power Sequencing: one 16-step sequence per space
- - Presets: up to 64 per space configurable via local UI
- - Zone control: up to 16 zones per space
- Monitoring Per Circuit:
- Breaker-trip notification
- Relay state
- Current draw, phase voltage, and energy usage
- Monitoring Per Space:
- Active sequences, presets, and clock events
- Zone levels
- DMX or sACN input
ACCESSORIES
- 0-10 Dimming Option
- 24 outputs of 0–10 V sink dimming control rated for 100 mA per output
- Contact Input Option
- 24 dry contact inputs which can be used to:
- trigger presets and sequences, which will play at the priority configured for architectural sources, or;
- directly control one or more outputs. The priority of these outputs is configurable. If nothing is configured, the last action takes precedence
- DALI Control Option
- 24 control loops of broadcast DALI control
- Each loop supports up to 64 ballasts
- External DALI power supply required
- RideThru Option
- Short-term power backup of control electronics
- Automatically engages when power is lost
- Recharges during normal power operation
- UPS Backup Kit for Load Shedding
- Allows Power Control Processor to be powered via external
- UPS (by others)
- Required for load shedding applications
- UPS provides power to drive relays off when normal power is lost
- UPS for each Sensor IQ panel must by UL 924 Listed and
- rated for a minimum of 200 W peak load
- Branch Circuit Fuse Kit
- Aids engineers in selective coordination* of
- emergency circuits