ETC IQ B20-277

ETC IQ B20-277

ETC IQ B20-277

ETC IQ B20-277

Sensor IQ circuit breaker, 20A, 1P, 240/277V

SKU: ETC-CB1062-2
Call for Price

Overview

ETC’s Sensor IQ Intelligent Breaker System provides mains-fed power distribution for up to 48 branch circuits in the industry’s most compact footprint. Sensor IQ breakers combine high-inrush rated overcurrent protection, switched power control, and power usage/breaker status reporting in a single device. With built-in station and sensor support via contact input, DMX and Ethernet connectivity, and optional 0–10 V dimming or DALI output, Sensor IQ panels easily integrate into a broad range of systems and applications.

APPLICATIONS

  • Theaters
  • Schools
  • Houses of worship
  • Conference centers
  • Stadiums and arenas

Features

  • Main Feed: 240/415 V or 277/480 V four-wire plus ground
  • 12-, 24- or 48-position breaker subpanel
  • Breakers
    • Hydraulic magnetic breaker with high inrush trip curve
    • 14 kA SCCR (or 65 kA series rated with main fuse)
    • Freely mix one-pole breakers up to 30 A
    • Integrated air-gap relay switching
    • Integrated on/off/tripped and connected load feedback
    • No power required for relay operation at the breaker
  • DMX and Ethernet (sACN) control of preset and sequence playback
  • Local user interface provides:
    • Panel configuration
    • Preset and sequence programming and playback
    • Individual channel control
  • Built-in Ethernet port
  • Available 0–10 V, contact input, and DALI control cards
  • UL924 Listed emergency control bypass contact input with load shedding

Specifications

REGULATORY AND COMPLIANCE

  • Breakers Listed to UL 489
  • Enclosures Listed to UL 67, UL 508, UL 924
  • Complies with ANSI DMX512-A standard
  • Complies with ANSI E1.31 streaming ACN standard

USER INTERFACE

  • Graphical display
  • Button interface
    • 0–9 number entry
    • Up, down and back-arrow navigation with enter
    • Test shortcut for local activation of preset, sequence and set level overrides
  • USB interface for uploads of setup and software updates

BREAKER

  • Hydraulic magnetic breaker maintains trip curve through entire thermal range, reducing nuisance tripping
  • Supports 15, 20 or 30 A single-pole breakers
  • Utilizes stab on bus connection
  • 50/60 Hz frequency
  • Inrush-pulse tolerance: 25 times rated current for half-cycle
  • Integrated hall-effect sensors detect contact positions
  • Integrated solenoid for remote operation
  • Trips on overload even if handle is forcibly held in the “on” position
  • Maintains trip curve through entire thermal range, reducing nuisance tripping
  • Load lugs accept 6–14 AWG load wiring
  • Multi-conductor rated output terminal
  • Integral mechanically held air gap relay
  • Manual control of relay state using breaker handle without power
  • Integral current sensing
  • Control and status provided by contact pads directly at bottom of the breaker case. No external wires or connections required for control or feedback
  • Remote Feedback for breaker state, breaker type, current draw and phase voltage
  • Visible state indication:

LED

Handle

Indication

LED on

Handle on

Output active

LED off

Handle on

Remotely controlled off

LED off

Handle off

Breaker tipped/Manually off

BREAKER CONTROL OPERATIONAL RATINGS

  • No load-remote switching: 1,000,000 cycles
  • 24 A Resistive (30 A breaker): 100,000 cycles
  • 16 A Resistive (20 A breaker): 100,000 cycles
  • 12 A Resistive (15 A breaker): 100,000 cycles
  • 15 A Electronic ballast (LED): 100,000 cycles
  • Handle operations: 10,000 cycles
  • Duty cycle of 6 full cycles (12 operations) per minute
  • Supports voltage isolation of 400 V RMS
  • Utilizes latching state relays

MECHANICAL

  • Enclosure constructed of 16-gauge steel finished in black, fine-textured, scratch-resistant powder coat pain
  • Removable outer panel includes integral locking door to limit access to electronics, breakers and local relay overrides
  • Full front access with no side clearance required
  • Removable covers for access to Class 1 and Class 2 wiring
  • Complies with California building code - seismic zone four
  • ELECTRICAL
  • Mains feed power input: 240/415 V or 277/480 V four-wire plus ground
  • Max current input:
    • IQ12-240 / IQ12-277 - 100 A
    • IQ24-240 / IQ24-277 - 200 A
    • IQ48-240 / IQ48-277 - 400 A
  • Quiescent draw: <10 W with relays at steady state
  • Optional isolation between chassis and equipment grounding
  • Short-circuit rating: 10,000 A, 14,000 A or 65,000 A symmetrical (See chart below)
  • Overloads occurs at 50 operations of 600% of rated current
  • Integrated current transformer
  • Current measurement range of 1–30 A. The maximum crest factor of primary current is 2.5
  • Feeder entry supported at top or top side
    • Bottom or bottom side entry supported by rotating enclosure during installation
  • Load wire entry supported on top, sides or bottom