Overview
The Echo Relay Panel Feedthrough is a control-oriented switching and power control built with today and tomorrow’s lighting loads in mind. Freely mix normal and emergency 120–347 V single-pole loads and either 120/208 V or 277/480 V double-pole loads in the same enclosure. With built-in station and sensor support via contact input, DMX and Ethernet connectivity, and optional 0–10 V dimming or DALI output, Echo Relay Panels easily integrate into a broad range of systems and applications.
APPLICATIONS
- Houses of worship
- Ballrooms and convention centers
- Multi-purpose rooms
- Arenas and stadiums
- Entertainment facilities with DMX control
- Retrofits for lighting systems with existing breaker panels
Features
- 120–347 V single-pole and 120/208 V or 277/480 V double-pole switching
- Up to 48 relays per panel
- Switches all relays at once or with configurable delay
- Mechanically latching relays fully rated for 20 A
- Single-pole relay kits fed by 120 V with 20 A branch breakers are suitable for plug load control
- Manual ON/OFF override with position indication
- Relays support field installation and replacement
- DMX and Ethernet (sACN) control of preset and sequence playback
- Local user interface provides:
- Panel configuration
- Preset and sequence programming and playback
- Individual channel control
- Built-in Ethernet port
- Available 0–10 V, contact input, and DALI control cards
- UL924 Listed emergency control bypass with load shedding
- Voltage barrier for normal/emergency mixed use panels
Specifications
REGULATORY AND COMPLIANCE
- cULus Listed
- UL508 Listed
- UL924 Listed
- Complies with ANSI E1.11 DMX512-A standard
- Complies with ANSI E1.31 streaming ACN standard
USER INTERFACE
- Graphical display with LED backlight
- Button interface with:
- 0–9 number buttons
- Up, down, back and enter navigation buttons
- Test shortcut for local activation of preset, sequence and set level overrides
- USB interface for upload of setup and software updates
MECHANICAL
- Panel consists of enclosure, covers with locking doors, and internal subpanels
- Enclosure constructed of 16-gauge steel finished in black, fine-textured, scratch-resistant powder coat paint
- Removable conduit panels on top, bottom and sides
- Full front access with no side clearance required
- Removable covers for access to Class 1 and Class 2 wiring
- Locking doors allow controlled access to manual override switch of each relay and Class 2 wiring only
- All low-voltage wiring is physically separated from AC by a mechanical barrier
- Removable subpanels containing the electronics and relays can ship separately – contact ETC
ELECTRICAL
- Discrete feed per circuit supports mixed voltage in a single panel
- Single panel for up to 48 relays, populated in any combination of single- or double-pole
- Separate wiring chambers for Class 1 and Class 2 terminations
- Optional voltage barriers install without tools between relays for separation of normal and emergency circuits
RELAY RATINGS
- 20 A 347 V General Purpose
- 20 A 347 V Ballast (HID)
- 20 A Tungsten
- Motor Loads:
- 5 HP @ 120 V
- 5 HP @ 240/277 V
- SCCR: 18,000 A @ 277 V (1P); 5,000 A @ 277 V (2P & 480)
- Inrush: 2000 A (1P only)
- Isolation: 2,500 V RMS
- State: Latching
- Relays are mechanically held
- Life: 60,000 operations at full load
- Terminal: Accepts 14–10 AWG copper wire
ENVIRONMENTAL
- Thermal: 0°C to 40°C (32°F to 104°F) operating temperature
- 20 A relay - 60 BTU/hr (estimated)
- Humidity 10%–90%, non-condensing
CONTROL ELECTRONICS
- Input: 120 or 277 V (+/-15%), 50/60 Hz, ≤ 16 A
- Multi-tap transformer terminals accept up to 12 AWG wire
- Control wiring terminations:
- Control terminals accept maximum of 12 AWG wire
- Control wiring exiting the panel are Class 2
- All control terminations utilize removable connectors
FUNCTIONAL
- Relay modes: Normal (priority/HTP), latch-lock or last-action
- System-Wide control
- DMX or sACN input
- Per-circuit patching
- Per-circuit threshold
- 0–200 prioritization
- Configurable data loss behavior:
- Play preset; Hold last look; Wait and fade
- UL 924 emergency lighting with load shedding
- Application/Space segmented Control
- Space segmenting: up to 16 spaces per panel
- Power Sequencing: one 16-step sequence per space
- Presets: up to 64 per space configurable via local UI
- Zone control: up to 16 zones per space
- Monitoring Per Circuit:
- Breaker-trip notification
- Relay state
- Current draw, phase voltage, and energy usage
- Monitoring Per Space:
- Active sequences, presets, and clock events
- Zone levels
ACCESSORIES
- 0–10 V Dimming Option
- 24 outputs of 0–10 V sink dimming control rated for 100 mA per output
- Contact Input Option
- 24 dry contact inputs which can be used to:
- Trigger presets and sequences, which will play at the priority configured for architectural sources, or;
- Directly control one or more outputs. The priority of these outputs is configurable. If nothing is configured, the last action takes precedence
- 24 dry contact inputs which can be used to:
- DALI Control Option
- 24 control loops of broadcast DALI control
- Each loop supports up to 64 ballasts
- External DALI power supply required
- RideThru Option
- Short-term power backup of control electronics
- Automatically engages when power is lost
- Recharges during normal power operation
- Tamper-proof Hardware Kit
- Special screw heads prevent access to panel interior